U-15800 Compiled Q&A Related to
Technical Conferences 2008 PA 295 January
5-6, 2009
|
|
Renewable Portfolio Standard (RPS) Procedural
(RPS-100) Surcharge
(RPS-200) Avoided
Cost/Transfer Price/Life Cycle (RPS-300) Renewable
Energy Credits (RPS-400)
Energy Optimization (EO)
Procedural
(EO-100) Surcharge
(EO-200) State
Administered Plan (EO-300) Self-Directed
Plans (EO-400) Performance
Evaluation/Energy Savings Calculations (EO-500) U-15800
Order Clarification (EO-600)
|
Renewable Portfolio Standard (RPS) Questions
|
| Procedural (100) |
Contact: Tom Stanton |
|
- Q-RPS-100-1. If a company's Renewable
Energy Plan and Energy Optimization Plan are filed in the same case
(that is, same Docket Number), can they be approved separately by the
Commission?
A-RPS-100-1. Yes. The Commission may approve
either plan separately, without simultaneously approving the other.
Staff recommends the two plans (RPS and EO) be filed as two separate
documents, even if that necessitates duplicating parts of the two
documents. However, providers can choose to file one document combining
the two plans.
- Q-RPS-100-2. The Temporary Order (pp. 16,
22-23; Attachment D, p. 5) clarifies the types of contracts the
Commission will require to be approved. It has been proposed to exclude
any contract with a value of less than $5 million, so as to provide a
clear threshold for contract submittal and approval. The Order does not
appear to include the proposed exclusion of contracts with a value of $5
million or less.
A-RPS-100-2. Correct. The Temporary Order did not adopt
the proposed $5 million exclusion.
- Q-RPS-100-3. What is the
expected duration of RPS reconciliation proceedings (the legislation
appears to presume that reconciliation proceedings will be concluded
within 90 days (Section 21(9))?
A-RPS-100-3. Plan modification cases have to be
completed within 90 days, but Section 49, regarding reconciliation
cases, does not impose a 90-day limit.
- Q-RPS-100-4. When will the Commission
determine when the annual report (Section 51) and, concurrently, the
renewable reconciliation proceeding is filed with the Commission?
Should the utility make recommendations in its renewable energy plans?
A-RPS-100-4. The Commission will make this decision some
time in the future. Staff welcomes recommendations.
- Q-RPS-100-5. Contract Approval – Will the
MPSC approval of contracts submitted in the case docket satisfy the
capacity review requirement contained in Section 6j(13)(b) of PA304
(460.6j(13)(b))?
A-RPS-100-5. Staff believes this is the intent of the
legislation, but Staff recommends that utility filings simultaneously
request both approvals.
- Q-RPS-100-6. Contract Approval – Will the
MPSC approval of contracts submitted in the RPS case docket satisfy the
capacity RFP requirements issued in MPSC Cases No's. U-12148 (Consumers
Power)/U-12177 ( Detroit Edison)?
A-RPS-100-6. Yes. Staff believes the new legislation
supersedes these orders, for the purposes of the RFP requirements for
capacity solicitations. Staff expects the Commission may revisit these
Orders, in light of the new legislation.
- Q-RPS-100-7. What compliance requirement
should the Company plan for in 2029 (i.e., full compliance year or
prorated)?
A-RPS-100-7. Full compliance: this question can be
argued and discussed in plan filings. Providers who believe that
prorated compliance would suit them better are free to suggest that to
the Commission.
- Q-RPS-100-8. Questions concerning the Act
will continue to arise. Will there be a formal process for
asking/answering questions?
Q-RPS-100-8. Yes. An on-line system will be established
for accepting and answering questions.
- Q-RPS-100-9. When will the Commission
establish the process for verification of credits for Advanced Cleaner
Energy Systems?
A-RPS-100-9. The process for verification of credits for
Advanced Cleaner Energy Systems will be established via the contractor
who is selected to run the renewable energy credit certification and
tracking program. This will be accomplished as soon as possible through
a competitive bid process.
- Q-RPS-100-10. Are the written questions asked
during the Technical Conferences incorporated in the transcripts?
A-RPS-100-10. Yes.
- Q-RPS-100-11. How can we get a copy of
the Technical Conference transcripts?
A-RPS-100-11. They are available electronically on the
Commission web site under E-Dockets. Search for Case No. U-15800.
- Q-RPS-100-12. Has the set of filing
deadlines for Municipal Utilities to be filed some time after Dec. 14
been filed? If not, when will it be?
A-RPS-100-12. All municipally-owned electric utilities
must file their renewable energy plans and energy optimization plans by
April 3, 2009 per the Commission’s 1/13/09 Order in Case. No. U-15800.
- Q-RPS-100-13. Please clarify what “filing
jointly” means. To what extent can utilities using a common set of
programs and a common approach to implementation file a common document
describing their joint approach?
A-RPS-100-13. For municipals, where it is a comment only
proceeding, filing jointly may just mean using the same binders with
separate dividers (or the electronic equivalent). For contested case
proceedings, filing jointly means that parties with common interests
and/or common representation will package their filings (maintaining
their individual docket numbers) together for simultaneous processing.
This would result in a single prehearing conference with a single
administrative law judge, and ultimately a single, combined schedule for
cross-examination of witnesses. Providers may choose to propose anything
up to identical programs at their discretion. Joint Plan filings should
clearly indicate what Plan is being proposed by each provider.
- RPS-100-14. What is considered a
"hydro" facility as far as it relates to the RPS defintion?
A-RPS-100-14. For purposes of PA 295, the following is
listed as NOT qualifying as a Renewable Energy System (Section
11(k)(ii)): "A hydroelectric facility that uses a dam constructed after
the effective date of this act [October 6, 2008] unless the dam is a
repair or replacement of a dam in existence on the effective date of
this act or an upgrade of a dam in existence on the effective date of
this act that increases its energy efficiency."
Thus, for purposes of PA 295, the law is not
going to allow inclusion of hydroelectricity from any new dams being
constructed, but Michigan has an estimated 600 dams that were in
existence when the act became law that had no hydroelectricity
production at that time, and 100 dams that were in existence then and
did generate hydroelectricity. My understanding is that any of the
first 600 could now be retrofitted to produce hydroelectricity that
would qualify, and any of the latter 100 could be repaired, replaced, or
upgraded with increased efficiency.
Plus, I don't think there are any limits to
energy produced from "Kinetic energy of moving water, including...
waves, tides, or currents [and] water released through a dam."
(Those definitions are in Section 11(i).)
- Q-RPS-100-14. Is a biodiesel blend is
considered a renewable fuel for participating in the CLEAN,
RENEWABLE, AND EFFICIENT ENERGY ACT 295.
A-RPS-100-14. E electricity
produced and used or electricity delivered to the grid can qualify for
renewable energy credit certification under Act 295, to the extent that
the fuel is a biomass fuel. So, for example, if the fuel is 20%
biomass derived biodiesel, then you’d be entitled to earn a 1 MWh REC
each time you produce and deliver (either for your own use or back to
the grid) 5 MWh of total energy. There could be extra credits in
terms of Michigan incentive RECs, which you could calculate based on a
careful reading of those rules. In order to get certified, I
expect you’ll need utility-grade metering to capture the required
information about how much you produce and use on-board and how much you
produce and deliver to the grid.
Before long,
there will be a certification and tracking system set up, and the
C&T agent will make clear exactly what the process will be.
In 2008 PA
295, you should carefully study:
- The definition of biomass (in Section 3);
- Renewable Energy Credits (defined in Section 9
and discussed in Section 41);
- Section 39(1)(a) and Section 39(2); and,
- Section 41
TOP
|
|
Surcharge (200) |
Contact: Tom Stanton |
- Q-RPS-200-1. Regarding Renewable Energy (RE)
surcharges, Section 45 of PA 295 allows for the imposition of RE
surcharges on a "per meter" basis. By definition, unmetered
service does not involve a meter, and, therefore, can not be subject to
any "per meter" surcharges. Moreover, in direct contrast to its
treatment of EO surcharges on unmetered service under section 89 (2),
the Michigan Legislature made no provision whatsoever for imposing
Renewable Energy surcharges on unmetered service customers under section
45. In recognition of these facts, do the utilities recognize that
it would be improper and unlawful to impose any Renewable Energy
surcharges on unmetered service customers?
A-RPS-200-1. On page 40 of the Temporary Order, the
Commission found that unmetered service will be included in the recovery
of the incremental cost of compliance for renewable energy plans. Staff
assumes that individual providers will file their plans and propose
options for treatment of unmetered customers, The Commission will make
its decision in the final plan orders.
Staff would note that for some “unmetered customers”
such as street lighting, individual consumption is determined by knowing
the power consumption of a device, which in Staff’s opinion is
functionally equivalent, for this purpose, of being a “meter”.
- Q-RPS-200-2. Staff has encouraged electric
providers to include in their Renewable Energy Plans provisions to
purchase renewable energy from residential and small commercial
customer/suppliers through an Advanced Renewable Tariff (ART) under
which a standard offer price would be provided for energy generated by
various technologies. We understand that the staff would like one or
more pilots proposed before February 20, 2009. Presumably, any
incremental cost associated with the ART purchases would be recovered
through the renewable energy itemized charge provided in PA 295 Section
45. Given that this approach does not appear to be consistent with PA
295, section 33, can staff provide the legislative authority to allow
the Commission to approve a renewable energy plan that contains such
purchases or to allow the Commission to approve the recovery of the
incremental costs in the section 45 "itemized charge".
A-RPS-200-2. Since this issue primarily concerns only
Detroit Edison and Consumers Energy, Staff will discuss it with them
outside of this forum.
- Q-RPS-200-3. How long will the RPS
surcharge be in place? 20 years starting in September 2009 (i.e. through
August 2029) or only during the
20-year compliance period ending
June 1, 2029?
A-RPS-200-3. Staff assumes the RPS surcharge will be
recovered over a 20‑year period, starting with the first billing month
of collection associated with an approved plan. However, this issue
should be addressed by providers in their plan filings for ultimate
determination by the Commission
- Q-RPS-200-4. Will the RPS surcharges be
implemented on a bills-rendered or service-rendered basis or should the
electric provider include a proposal in its renewable energy plan?
(Note that a utility company prefers bills rendered.)
A-RPS-200-4. Providers are invited to make a proposal
regarding this issue in their plans.
- Q-RPS-200-5. The Renewable Energy Plan
Surcharge Summary Table is the same in Attachment A (IOUs) and
Attachment C (munis). Do the municipally-owned utilities need to provide
the same level of detail as the investor-owned utilities?
A-RPS-200-5. These are general templates. If a portion
does not apply, either show a zero value or leave the rows or columns
out. The purpose of the tables is to help determine the expected
incremental cost of compliance or what portion of the energy and RECs
that were generated or purchased should be recovered through the
surcharge (versus what portion should be recovered in general rates).
Per Sec. 7(b), "Incremental cost of compliance" means the net
revenue required by an electric provider to comply with the renewable
energy standard, calculated as provided under section 47.
- Q-RPS-200-6. If electricity is provided to an
end user pursuant to a long-term fixed price contract, is it permissible
to charge the customer for the cost to implement the Renewable Energy
Plan?
A-RPS-200-6. Yes. Section 89(2) of the statute requires
the provider to implement a per meter charge. Unmetered electric
customers will also be charged. A provider who wishes to waive customer
surcharges under certain circumstances should describe the circumstances
to the Commission in its plan filing.
- Q-RPS-200-7. Is there a spreadsheet with formulas for
ATT A – Renewable Energy Plan Surcharge Summary?
A-RPS-200-7. There is a spreadsheet but it does not
contain formulas. The inputs would likely be generated from other source
documents. A table has been created to provide more explanation of the
line items in ATT A and is attached as a separate document.
- Q-RPS-200-8. What does the acronym BOT mean in ATT A?
A-RPS-200-8. Build Own Transfer, which was a reference
to wording in an earlier version of the PA295 legislation and so this
language no longer applicable.
- Q-RPS-200-9. How is the transfer price used in the
calculation in ATT A? Is it used to put a portion of the cost of the
renewable program in the PSCR, with the remainder to go into the
surcharge?
A-RPS-200-9. Yes, the transfer price (line item 40 in
the attached document) multiplied by the RECs obtained through
generation (line item 35) becomes the revenue recovered by the provider
in their PSCR process (line item 42). Section 47 of PA 295 describes the
items that flow into the incremental cost of compliance. (See DTE slide
captured below)
- Q-RPS-200-10. Should the transfer price represent an
estimate of the long term capacity and energy costs avoided by the
renewable energy program?
A-RPS-200-10. Yes
- Q-RPS-200-11. Are the “Revenue Requirement” in ATT A to
be calculated only for the “Required RECs” which are determined in the
upper section, such that the cost of existing renewable is not included
in the calculation of the surcharge?
A-RPS-200-11. Yes, the revenue requirements (line items
25-29) apply only to new RE activities.
- Q-RPS-200-12. How should the Michigan allocation of
renewable resources undertaken to meet the Wisconsin RPS after the
implementation of Act 295 be handled? Are they considered new renewable
resources and included in the surcharge calculation? Or are they
considered existing renewable resources and in this way excluded from
the MI surcharge.
A-RPS-200-12.
- Q-RPS-200-13. Should lines be added to the template to
compare the cost of renewable plan to the generic coal plant less EO
savings as required by Sec 21 6 b of the Act.
A-RPS-200-13. For clarity, it is recommended this
comparison be done on a separate sheet because it utilizes item not
directly related to RE surcharges.
TOP
|
| Avoided
Cost/Transfer Price/Life Cycle (300) |
Contact: Tom Stanton |
- Q-RPS-300-1. Any clarification on the use
of the "ultra-supercritical pulverized coal plant" as the facility for
determining the expected lifecycle cost of electricity generated by a
new conventional coal-fired facility.
A-RPS-300-1. Staff will clarify this during discussions
with Providers, in preparation for submitting to the Commission the
“guidepost” or “hurdle rate” as directed in the Commission Order (p.
24). Staff’s current thinking is that the standard should be
“supercritical” rather than “ultra-supercritical” as we previously
advised the Commission.
- Q-RPS-300-2. To the best of our knowledge, no
depreciation schedule exists for a wind turbine. Based on the wind
turbine manufacturer’s recommendation of a 20-year useful life for wind
turbines, we are assuming a 20-year depreciation for wind turbines. Does
the commission share this view of 20-year depreciation for wind
turbines? If so, will the commission issue an order establishing a 20
year depreciation for wind turbines for the purpose of the renewable
plan filing?
A-RPS-300-2. As providers develop their plans,
determination of reasonable asset lives is something they need to
develop and submit with their plans. Staff’s preliminary thinking is
that 20 years may be reasonable. Staff assumes that the Commission will
adopt a reasonable useful life in the plan approval orders.
- Q-RPS-300-3. Is the renewable energy charge
supposed to be designed so that all costs (including all capital costs)
incurred to meet the RPS requirements for the 20‑year period of the
renewable energy plan are recovered within the 20-year period? I.e., is
the charge intended to result in all plant investments made to comply
with the RPS standard being fully depreciated at the end of the 20
years? If the answer to either question is "no," then what is the
mechanism for recovering any remaining costs after the end of the
20-year period?
A-RPS-300-3. No. At the end of the 20-year period, any
remaining balances in the RPS Plan asset account need to be proposed for
inclusion in plant-in-service in the next available rate proceeding.
- Q-RPS-300-4. Determination of Transfer Price –
Will the setting of the transfer price by the MPSC in an RPS
reconciliation proceeding support the reasonableness and prudence of
expense per Section 6j(12)?
A-RPS-300-4. Staff expects so. Providers may wish to ask
the Commission in the RPS reconciliation proceeding to make a
determination that it is a reasonable and prudent transfer price for
purposes of an Act 304 hearing.
- Q-RPS-300-5. In Commission Order U-15800,
Item #4 Calculation of the incremental cost of compliance via the
transfer price to be recovered through the PSCR clause; the second
paragraph says that the transfer price of EPC contracts, contracts
for renewable energy systems that have been developed by third parties
for transfer of ownership will have a transfer price established as a
floor for the lifecycle of the project. The Order goes on further
to say that provider owned projects will have transfer prices set in
vintages. The Order is silent on what the transfer price should be
for renewable energy systems developed by third parties that will not
have an ownership transfer.
A-RPS-300-5. It is unnecessary to vintage the
third-party owned PPAs because they are operating under
Commission-approved contracts and the utilities will be allowed to
recover all costs associated with those contracts.
If a provider believes it needs the same treatment for
PPAs that will not have an ownership transfer, it should ask for such
treatment when it files its plan.
- Q-RPS-300-6. Indicate if there are
guidelines for how often the life cycle cost of new conventional coal
will be recalculated?
Q-RPS-300-6. Anytime you have a new plan, you have
to re-calculate the hurdle rate.
TOP
|
| Renewable
Energy Credits (RECs) (400) |
Contact: Julie
Baldwin |
- Q-RPS-400-1. PA 295 Section 35 (1)(b) provides
that with regard to the ownership of renewable energy credits associated
with energy obtained by an electric provider under a PURPA PPA, if a
separate agreement in effect on January 1, 2008, the separate agreement
shall govern until January 1, 2013. In some cases those agreements do
not identify the generator that originated the RECs. What level of proof
that a separate agreement applies to energy generated under a PURPA
agreement does the Commission expect electric providers to meet in its
Renewable Energy Plans?
A-RPS-400-1. This is something the provider and
generator must work out among themselves. The generator originating the
RECs must be identified in order for the RECs to be certifiable.
- Q-RPS-400-2. PA 295, Section 41 (4) requires
the Commission to establish a renewable energy certification and
tracking program. Please provide the Commission's timetable for
establishing the certification and tracking system. Will there be a fee
for this service? Will the Providers include this fee in their proposed
plans?
A-RPS-400-2. The Commission will establish this as soon
as possible. Staff expects the certification and tracking system to be
ready by the time that plan implementation begins. Certification and
tracking fees are expected to be paid by the generators.
Typically, the way these systems work, the generator
applies for certification, pays a pretty small fee, gets their REC
certified. The only other charges are associated with transfer of the
certificates and the people transferring the certificates pay a small
fee at that time. If the provider is going to own the generation, Staff
would expect the fees paid by the generators to be included in the
expenses in the provider’s proposed plan.
- Q-RPS-400-3. PA 295, Section 41 (4)
requires the Commission to establish a renewable energy certification
and tracking program. For RECs that result from generation occurring
prior to the time the renewable energy certification and tracking
program is established, what procedures are expected to be established
to retroactively certify and track those RECs?
A-RPS-400-3. Providers and generators can begin keeping
track of Michigan-qualifying RECs now, in anticipation of certification
later. To prevent problems with retroactive certification, Staff
recommends that all data deemed necessary in order to insure
certification should be carefully recorded and documented now.
- Q-RPS-400-4. PA 295, Section 39 (1)
provides that a renewable energy credit shall be granted for each
megawatt hour of electricity generated from a renewable energy system.
PA 295 section 11 (k) defines a renewable energy system as a facility or
electric generation system that uses one or more renewable energy
resources to generate electricity. PA 295 section 11 (i) to mean a
resource that naturally replenishes over a human time frame and that is
ultimately derived from solar power and includes, but is not limited to,
(i) biomass. PA 295 section 3 (f) defines biomass to include,
but not limited to, (iv) trees and wood, but only if derived
from sustainably managed forests or procurement systems, as defined in
section 261c of the management and budget act. Will the Commission grant
renewable energy credits for each megawatt hour of electricity generated
from a renewable energy system that uses trees or wood from sources
other than a sustainably managed forest of procurement system such as a
right of way clearing project or construction debris disposal
operation?
A-RPS-400-4. The Act’s definition of “renewable energy
resource… includes but is not limited to” certain types of biomass
materials (Section 11(i)). Staff cannot anticipate what the Commission
will do.
- Q-RPS-400-5. There appear to be no
alternative compliance payments for RECs. Therefore, is there no
ceiling on the market prices for RECs in the future?
A-RPS-400-5. Correct. The Act does not set any ceiling
on the market price for RECs. Because RECs can be produced any number of
ways (purchased, generated or bought from a renewable facility under
contract), the market should provide RECs at a reasonable price.
- Q-RPS-400-6. Can providers use existing
Renewable Portfolios to meet Act 295 RPS requirements? If so, can they
be used for 100% of their needs, as long as the RECs are active and have
not expired? Is there a cap on RECs used?
A-RPS-400-6. Subject to all of the limits in Sections
29, and 41, pre‑existing renewable energy resources can be used to meet
Act 295 RPS requirements, for RECs generated after October 6, 2008.
Pre-existing renewable resources can be used to meet 100% of a
provider’s needs (except for Consumers and Detroit Edison, who have
build-out requirements). The Act does not appear to establish any cap on
the number or percentage of RECs used which come from pre-existing
renewable resources.
- Q-RPS-400-7. When coming up with a provider’s
Renewable Energy Portfolio, and calculating the number of renewable
energy credits equal to the number of megawatt hours of electricity
produced or obtained in the 1-year period preceding October 6, 2008, can
a provider count RECs that were sold to other parties as Green-e
certified RECs? Can a provider count RECs that were used to provide
service to customers in the provider’s Green Pricing program?
A-RPS-400-7. It is Staff’s understanding that Michigan
RECs did not exist prior to October 6, 2008. RECs not owned by a
provider cannot be counted by that provider. RECs sold to retail
customers in a Green Pricing Program cannot be counted towards
compliance with PA 295.
- Q-RPS-400-8. When should Michigan
incentive RECs associated with Ludington pumped storage generation be
accrued, when the off-peak period renewable energy is generated and the
facility is pumped or when the facility ultimately generates
energy?
A-RPS-400-8. RECs associated with Ludington pumped
storage generation should be accrued when the storage facility
ultimately generates on-peak energy.
- Q-RPS-400-9. For purposes of determining
its RPS requirements for 2012 through 2015, should an electric provider
include in its pre-existing portfolio Advanced Cleaner Energy Credits
that would have been transferred to it in the year prior to enactment of
PA 295?
A-RPS-400-9. No. It is Staff’s understanding that
Section 27(3)(a)(i) indicates only renewable energy credits should be
included, and does not include any provisions for substituting Advanced
Cleaner Energy Credits.
- Q-RPS-400-10. Does the percentage of
renewables in a provider’s supply portfolio go up as overall sales are
reduced by actions taken as a result of the Energy Optimization
Plans?
A-RPS-400-10. Yes. It is a
percentage standard. Net sales reductions from any cause, including the
EO Plan, will reduce overall sales volumes used as a base to calculate
the RPS targets. This would increase the relative amount of renewable
supply sources in a provider’s portfolio.
- Q-RPS-400-11. Would a facility in Minnesota
qualify for the Michigan RPS? Section 29 describes… "...located outside
of this state in the retail electric customer service territory of any
provider that is not an alternative electric supplier...". So, to
qualify, an out-of-state facility has to be in the territory of
a provider who is not an alternative electric supplier...what
does that mean?
A-RPS-400-11. Staff believes that renewable facilities
anywhere in the state of Michigan will qualify for Michigan's program.
RECs from generators outside of Michigan can qualify if
the facilities are inside the retail service territory of a regulated
utility that serves retail customers in Michigan. This would
include Indiana-Michigan Power Company and several Wisconsin
utilities. Unless the Minnesota facility is in the service
territory of a utility that also provides regulated electric service in
Michigan, its generation could not result in Michigan RECs
Section 29(e) contains a very specific provision
that covers not-for-profit providers from Indiana and Wisconsin.
“Alternate Electric Supplier” is the Michigan term
that means competitive electric suppliers.
(Note in section 29(1), a "provider" is a provider of
retail electricity in Michigan. Also see the definition for
"provider" in Section 9, and then Electric Provider in Section 5.)
- Q-RPS-400-12. Under Section 29 (2) (e) we
know that Midwest can use WVPA's renewable energy to meet its power
needs. Besides the generation and RECs we are using to determine
Midwest’s baseline (from Oct. 6, 2007 to Oct. 6, 2008) and what we have
used for our green pricing program and what we sold into the market, can
we use all of our remaining RECs to meet its needs? Are there any
other date requirements under Section 27(5) on fulfilling its future
needs?
A-RPS-400-12. Staff believes that the historical
number would be whatever system power Wabash delivered to Midwest during
the time period in question. If your average mix was 4% at that
time, then the starting point for Midwest would be 4%. It is
correct that you cannot count in the Oct 2007-Oct 2008 timeframe any
RECs generated by Wabash that were either: (a) sold to others so they
were no longer the property of Wabash; or (b) sold to end-use customers
as part of a green pricing program.
That is the purpose of setting the baseline.
Going forward, you can “assign” to Midwest any RECs that
“belong” to Wabash (given the caveats discussed in A-RPS-400-12 about
ownership and green pricing programs), so that Midwest in the future can
count a higher percentage.
- Q-RPS-400-13.Under the Clean, Renewable, and Efficient Energy
Act electricity generated using methane gas extracted from
abandoned coal mining operations would qualify for renewable energy
credits?
A-RPS-400-13. The answer is no, per Section 11(i):
"(i) "Renewable energy resource" means a resource that
naturally replenishes over a human, not a geological, time frame and
that is ultimately derived from solar power, water power, or wind power.
Renewable energy resource does not include petroleum, nuclear, natural
gas, or coal. A renewable energy resource comes from the sun or from
thermal inertia of the earth and minimizes the output of toxic material
in the conversion of the energy and includes, but is not limited to,
..."
TOP
|
|
Energy Optimization (EO) Questions
|
| Procedural
(100) |
Contact: Rob
Ozar |
- Q-EO-100-1. What procedures will be in
place to ensure that any self-directed plan and information submitted by
a customer will be kept confidential, as required under Section
93(6)?
A-EO-100-1. The Act exempts this information from FOIA.
Staff will develop procedures to implement these provisions. Documents
submitted to the Executive Secretary under this provision should be
clearly indicated as such, to prevent disclosure to anyone other than
Staff. Generally, parties seeking confidential treatment of filed
materials should file using either CDs or DVDs and a letter can be
submitted indicating that confidential documents have been filed that
are not available. They will then be secured in the Executive
Secretary’s office.
• Q-EO-100-2. Section 93(4) states that the Commission
shall, by order, provide a mechanism for recovery of costs from certain
customers for provider level review and evaluation, and for the costs of
the low income energy optimization program under Section 89.
A. When do you expect the Commission to issue that
order?
B. Do you expect the Commission to issue a single order
for all providers, or will the Commission issue a separate order for
each provider?
C. Alternatively, is the Commission expecting the
providers to propose mechanisms for recovering these costs in their
plans and the Commission will issue the required order when it approves
the plans?
A-EO-100-2. Staff expects separate orders for each
provider. Staff encourages providers to propose a preferred mechanism.
Staff believes it is likely that the Commission will include cost
recovery for these costs in its orders approving Energy Optimization
Plans.
- Q-EO-100-3. If the customer’s electric
provider has chosen not to administer its own energy optimization
program and instead elects the alternative compliance payment option
under Section 91, should a customer file its self-directed plan and
status reports with its electric provider, the state administrator, or
both?
A-EO-100-3. Both.
- Q-EO-100-4. If a provider chooses to comply
using the State Administered Plan, should the provider expect to prorate
the first year alternative compliance payment, or should they expect to
pay the entire amount, and collect the entire year's requirement with a
7- or 6-month surcharge?
A-EO-100.4. The alternative compliance payment amounts
are set by Section 91(1)(a) through (d). The Commission may adopt a
proration alternative when it approves the State Administered Plan.
Although the Commission has generally adopted a policy that allows
collection of energy optimization surcharges only after a provider's
plan is approved, Staff does not anticipate that the same type of
approval process will be used for the contract with the State EO Plan
Administrator. Therefore, providers may wish to petition the Commission
to begin collecting these amounts prior to the time when the State
Administered Plan is finalized and approved. This would be consistent
with the Commission's indication in the Temporary Order (p. 34):
“Beginning the surcharge as soon as possible will allow the costs to be
spread over more months, which will lower the monthly surcharge amount.”
Providers who have chosen to utilize the State
Administered Plan will still need to file for authorization for a
surcharge to recover the alternative compliance payment. Staff
recommends that those filings be made at the same time the other
providers are filing their plans for approval.
- Q-EO-100-5. How much input/control will
the provider have with respect to the Administrator's programs, or will
that totally be set by the MPSC?
A-EO-100-5. Input from providers will be limited to
participation in an advisory board that will work with the Commission
Staff and the contractor to resolve program design and implementation
issues.
- Q-EO-100-6. When are customers required to
elect self-directed treatment under Section 93(1) in 2009?
A-EO-100-6. The notice of intent to self-direct must be
sent to the provider by January 15, 2009. The Self-Directed Plan must be
submitted to the provider by January 30, 2009 (See U-15800,12/4/08, page
36.)
TOP
|
|
Surcharge (200)
|
Contact: Rob Ozar |
- Q-EO-200-1. Will customers of providers who
elect to make the alternative compliance payment under Section 91, and
who are subject to a Section 91 energy optimization surcharge, be
subject to a separate surcharge for a low-income energy optimization
program?
A-EO-200-1. No. Staff’s interpretation is that to be
consistent with Sec. 89(5) and Sec. 91(3), customers of a provider who
elects to make the alternative compliance payment under Sec. 91 (i.e.
chooses to participate in the State Administered EO Plan), will pay a
surcharge sufficient to allow the provider to recover the amounts
established in Sec. 91(1). If a customer is subject to a Section 91 EO
surcharge, they have not elected to self-direct under Section 93. Only
self-directing customers are subject to a separate surcharge to cover
low-income EO programs .
- Q-EO-200-2. Since large customers do not
need to utilize the services of an energy optimization service company
under Section (93)(4)(a), does the Staff agree that those customers will
not be subject to the costs under subdivision (a) for provider level
review and evaluation?
A-EO-100-2. Staff expects separate orders for each
provider. Staff encourages providers to propose a preferred mechanism.
Staff believes it is likely that the Commission will include cost
recovery for these costs in its orders approving Energy Optimization
Plans.
- Q-EO-200-3. Will a self-directed customer
be subject to any energy optimization related costs other than provider
level review and evaluation costs for smaller self-directed customers
and low income energy optimization program costs for self-directed
customers of providers operating their own energy optimization program?
If so, please identify the costs.
A-EO-200-3. No, but they will be responsible for the
costs associated with their own self-directed plan.
- Q-EO-200-4. Section 89 (2) of PA 295 stipulates
that any energy optimization surcharge imposed on electric customers who
use unmetered service must be "an appropriate charge". Which
factors will the utilities and the Commission utilize to determine
whether a proposed surcharge on unmetered electric customers is, in
fact, "appropriate"?
A-EO-200-4. These factors have not yet been determined.
Providers are invited to include proposals in their Energy Optimization
plan filings.
- Q-EO-200-5. Will the utilities
develop different EO surcharges for different types of unmetered
electric uses (e.g., government street lighting, traffic control
devices, cable power supplies, wireless access companies, and security
camera companies)?
A-EO-200-5. These factors have not yet been determined.
Providers are invited to include proposals in their Energy Optimization
plan filings.
- Q-EO-200-6. For those types of unmetered
electric customers whose electric use is not subject to any energy
optimization, is it understood that the appropriate charge should be
zero?
A-EO-200-6. No. Staff does not know what the Commission
will ultimately decide on this issue. However, Staff does not share the
questioner’s assumption that the charge would be zero.
- Q-EO-200-7. Unmetered power service is
unmetered because the amount of power used is too small to justify the
cost of metering the energy usage. Given this fact, is it
understood that any EO surcharge that may be imposed on unmetered
service customers must be substantially less than the surcharges imposed
on other types of customers who use far more
electricity?
A-EO-200-7. Staff does not agree with the initial
premise. Staff expects EO surcharges for unmetered customers will
generally be based on and differentiated by usage.
- Q-EO-200-8. Has any utility developed any
preliminary estimates of the surcharge(s), if any, that the utility may
impose on unmetered service customers?
A-EO-200-8. No, not to Staff’s knowledge.
- Q-EO-200-9. Please clarify with respect
to using the Independent Energy Optimization Program Administrator
regarding the revenue payments -- is the amount listed in the statute
(Section 91) a strict amount, or just a floor and thus the provider
could owe more?
A-EO-200-9. Staff believes those are fixed amounts.
- Q-EO-200-10. Page 32
regarding Gas Transportation customers - Item #3 "Treatment of
nonresidential natural gas customers", in section XI, Energy
Optimization Plan Issues and Clarifications on page 31, conflicts with
item #8 "Definition of Natural Gas Retail Sales for an IOU" in the same
section on page 37. Which is correct?
A-EO-200-10. In an amendatory December 23, 2008
Order in Case No. U‑15800, the Commission corrected the language on page
37 of its December 4 Order to read: “For the savings targets, the
percentage will be applied to sales volumes including gas customer
choice and gas transportation sales volumes.”
On January 2, 2009, ABATE filed in Case No. U-15800 a
Petition for Reconsideration and/or Rehearing and Request for Stay. The
Commission’s decision on that Petition may affect the ultimate answer to
this question.
- Q-EO-200-11. Please clarify the intent of
460.1089, section 89, (1) and (3). Are utilities allowed to spend more
than would be raised by the caps on cost recovery described in (3) if
the funds are being used for programs that are cost effective? If so,
does that mean that these caps can be exceeded in this circumstance?
A-EO-200-11. The intent of the legislation is to provide
a specific EO program that meets certain targets at certain cost caps.
If a utility wants to provide additional programs funded through another
means, the legislation doesn't’t prohibit this. Utilities who want to
provide EO programs beyond what is required by 2008 PA 295 would need to
seek approval from either the Commission or the municipal board.
- Q-EO-200-12. Can costs for program
delivery be included in the bills submitted by a Joint Action Agency for
municipal or cooperative utilities that is selected by Member Utilities
to collect revenues and expend program costs on behalf of its members?
A-EO-200-12. Staff believes this would be acceptable
assuming all affected parties agree. Cooperatives are subject to
Commission jurisdiction on this issue. Municipal utilities would need to
follow their own rate making processes.
- Q-EO-200-12a. Follow-up: Would the
individual entities within that group have to meet the standard
separately? Or would they all be considered one entity and collectively
have to meet the requirements?
A-EO-200-12a. Staff believes each entity would have to
meet the standards separately.
- Q-EO-200-12b. Follow-up: Would any costs
that the group incurred be divided among the entities and collected as
long as they are accounted for?
Q-EO-200-12b. When plans are filed, include those costs
and how you intend to work that out.
- Q-EO-200-13. Clarification: On the
payments to the State Administrator, the statute is clear in my mind
that you pay that amount that you owe to the Administrator for
implementation of the program. However, very likely the utility will
have additional expenses such as internal accounting expenses, other
program-related expenses if they have to add a staff person to handle
additional questions from customers. I anticipate there will be
additional expenses beyond just what they pay to the Administrator if
that’s the route that they select. Would you
agree?
And second: If the utility has additional
expenses beyond what they pay to the Administrator, will there be any
issue with recovering those costs in the surcharge? Or is that State
payment to the Administrator the most that the Commission will allow the
utility to recover in the surcharge?
A-EO-200-13. It is Staff’s opinion, subject to review by
the Commission, that the funds collected pursuant to Sec. 91(1)
represent the entirety of the EO surcharge and all of that has to go to
the State Plan Administrator. Additional expenditures will be the cost
of doing business as a utility.
If a municipal utility opted to go with the State plan
and pay the amount specified, they would have to deal with the cost
recovery through their own cost recovery process. Top
|
| State
Administered Plan (300) |
Contact: Karen Gould |
- Q-EO-300-1. When will the state plan
administrator be identified?
A-EO-300-1. The Commission is currently engaged in
a request for proposals (RFP) process to identify the state plan
administrator. Staff expects the administrator will be identified not
earlier than second quarter 2009.
- Q-EO-300-2. If a provider makes the
alternative compliance payment under Section 91, is the state
administrator then responsible for the low income energy optimization
program for that provider? Does the alternative compliance payment made
under Section 91 cover the costs for the low income energy optimization
program?
A-EO-300-2. The State Plan Administrator will act
as the provider for those providers who choose the alternative
compliance payment. Staff believes that the alternative compliance
payment would cover the costs for the low income energy optimization
program except for the contribution required of the self-directed
customers. Self-directed customers will effectively be reimbursing the
provider for their share of the low-income EO program.
Top
|
|
Self-Directed Plans (400)
|
Contact: Patricia Poli |
- Q-EO-400-1. Section 93(1) states that a
customer is not subject to certain energy optimization charges if the
customer files with its electric provider a self-directed energy
optimization plan. If the customer’s electric provider has chosen not to
administer its own energy optimization program and instead elects the
alternative compliance payment option under Section 91, what will be the
role of the electric provider in accepting and/or reviewing the
self-directed customer’s plan and status reports?
A. Who will review and evaluate the
self-directed plan, the electric provider, the state administrator, or
both?
B. Who will be responsible for monitoring the
customer’s progress towards the goals in the plan, the electric
provider, the state administrator, or both?
C. Can the state administrator reject a plan, or
can only the provider reject a customer’s self-directed energy
optimization plan?
A-EO-400-1. Subject to correction by the Commission or
the courts, the Staff believes the State Administrator will review and
evaluate the self-directed plan. The State Administrator will be
responsible for monitoring progress. For providers who opt to have the
state administrator implement their Energy Optimization programming, the
State Administrator will function in the role of provider for the
purposes of Subpart B: Energy Optimization (e.g., Sections 71 and 93).
- Q-EO-400-2. Section 93(5) requires the
self-directed plan to be a “multiyear plan.” Can a self-directed
customer’s plan be as short as two years?
A-EO-400-2. Yes. Two years is the minimum duration of a
self-directed plan, whether amended or not, as long as it is
operational. A plan may be terminated by the customer before the end of
the two year period.
- Q-EO-400-3. Section 93(8) permits a self-directed
customer to amend its plan. Does that include the ability to amend the
plan’s term? Will a customer be able to “opt out” of the self-directed
plan option prior to the end of its plan’s term? (i.e.: can the customer
self-administer a program for 1 year and then choose to no longer
self-administer?). Can customers that file a 3-year EO self direct plan
change their mind? For example, after two years can they come back to
the utility's program?
A-EO-400-3. Staff is not aware of any prohibition
against amending the term of a self directed plan. However, as stated in
A-EO-400-2, because of the statutory requirement that a self-directed
plan must be "multi-year", a self-directed plan may not be amended to a
term of less than two years. Staff expects customers to enter into
self-direct plans with the intent to meet the goals of the Act and while
a customer is engaged in a self-directed plan there will be regular,
measurable progress toward meeting the goals of that plan. Customers may
cancel a self-directed plan prior to the end of its term. Customers who
cancel a self-directed plan will become responsible for paying their
provider’s EO surcharge and will be eligible to participate in the
provider’s EO plan.
- Q-EO-400-4. Do customers that self-direct need only
achieve their target at sites where they want to make an EO investment?
In other words they don't have to do something at every location so long
as what they do at locations of their choice garners sufficient savings
to cover all sites.
A-EO-400-4. Staff believes that as long as the energy
optimization goals are reached, the customer is free to target energy
optimization investments to any of the customer’s participating
facilities. The details regarding the energy optimization proposals and
how the savings target would be achieved would be part of the customer’s
initial self-direct plan filing.
- Q-EO-400-6. If a customer does not file a self-directed
EO Plan by January 30, 2009 (as required by the Commission's Temporary
Order), does the customer get an additional opportunity to file a
self-directed plan in 2009?
A-EO-400-6. No. If there is any uncertainty about
whether a customer wants to self-direct or not, the customer is advised
to file a notice of intent to file by January 15, 2009 and submit a plan
to their provider by January 30, 2009 because the customer will have the
opportunity to terminate or amend the plan at any time before or after
it is implemented
- Q-EO-400-7. Is there a filing deadline for customers
opting to file a new self-directed plan that commences on 2010 or
subsequent years?
A-EO-400-7. In order to give the providers sufficient
time to incorporate the self-directed plan into the provider's EO Plan,
Staff would strongly encourage such filings to be made by November 15th
of the year preceding the expected date of plan operation (i.e. by
November 15, 2009 for a plan to be included in a provider's 2010
program.)
- Q-EO-400-8. Is there a filing deadline for customers
amending a self-directed plan that has been filed with its provider?
A-EO-400-8. No. Consistent with the provisions of Sec.
21(9) and Sec. 93(6), a customer may file an amendment at any time. This
may, or may not, necessitate an amendatory plan filing by the affected
provider.
- Q-EO-400-9. Self-directed plans are required to be
submitted by January 30. However, the State Administrator is not
expected to be identified until second quarter 2009. If the provider has
chosen the State EO Administrator, who does the customer submit the
self-directed plan to?
A-EO-400-9. The customer should submit the plan to the
Staff and the provider. Staff will pass the self-directed plans on to
the State Plan Administrator as soon as possible after they are chosen.
- Q-EO-400-11. What kind of monitoring would the Public
Service Commission be doing to ensure that they’re meeting the goals
that they put forward in their program? Will verification be simple
usage or actual implementation of measures?
A-EO-400-11. We do not anticipate sending staff auditors
out routinely to do a physical verification of installed measures.
However, some sort of independent verification that plan improvements
have been purchased, installed, and are in use, will be needed. Staff
expects proposals on this in the Plan filings.
- Q-EO-400-12. When will self-direct customer know what
the low income charges will be?
Q-EO-400-12. Surcharges will be known after the
relevant provider’s plan is approved by the Commission.
- Q-EO-400-13. The statute does not itself differentiate
between retail and wholesale customers for eligibility for the
self-directed EO plan. Eligibility is strictly limited and related to
the annual peak demand of the customer's sites covered by the
self-directed plan. Is that interpretation correct?
A-EO-400-13. Only retail customers are eligible for
self-directed EO plans. A wholesale for resale customer, per se, is not
eligible to participate in their provider’s energy optimization plan.
Rather, the wholesale customer will be providing an energy optimization
plan for its retail customers.
- Q-EO-400-14. Is the Self Direct Application available?
A-EO-400-14. Yes, the final version is posted on the
Spotlight box on the Michigan Public Service Commission Electricity web
page.
- Q-EO-400-15. Can temporary shut-downs at industrial
facilities be included in a self-directed plan as a conservation
measure?
A-EO-400-15. No. Sec. 93(5)(c)(i) prohibits counting
savings from “Changes in electricity usage because of changes in
business activity levels not attributable to energy optimization”.
Top
|
|
Performance
Evaluation/Energy Savings Calculations (500) |
Contact: Patricia Poli |
- Q-EO-500-1. How will the energy savings
from self-directed plans be measured? What will be the procedures for
normalizing for weather, production, and other
variances?
A-EO-500-1. There will be a statewide “deemed energy
savings” database that can be used for identifying savings associated
with common measures. Several requirements for these kinds of
calculations are included in Section 93,(5)(c). Consistency with the
calculation methods used by the customer’s provider will be desirable.
Self-direct customers should work with their providers to determine what
will be workable for them.
- Q-EO-500-2. When counting energy savings for
the EO targets and using a CFL bulb as an example, which saves 38 kWh
per year and has a useful life of 9 years – do we take credit for 38 kWh
each year for 9 years or do we take credit for the 342 kWh in the first
year (38 kWh x 9 yrs)?
Q-EO-500-2. Energy savings calculations will be
addressed for measures included in the Michigan energy savings database.
In this instance, the credit would be 38 kWh each year; not 342 kWh in
the first year.
- Q-EO-500-2a. Follow-up question: How
precise are we going to take that? In other words, if I put a CFL light
bulb in a customer’s home in July, do I take six months or do I take one
half of that 38 kilowatt hours in the first year, eight full years, and
then one half in the ninth year?
A-EO-500-2a: An evaluation
work group will work out some of the details.
- Q-EO-500-3. There may be a particular
situation where you have better information than the average would
dictate. In other words, the deemed savings for a CFL are based on an
average of a thousand CFL’s that you are putting in are used eight hours
a day rather than two hours a day, or whatever the deemed savings,
shouldn't’t you put that in your plan?
A-EO-500-3. The original answer (above) pertains
to this situation. If you do not use the database, then you will have to
provide documentation.
- Q-EO-500-4. Under Section 77(2),
providers are able to take advantage of load management to achieve
energy savings. What credit is given in a self-directed energy
optimization plan for demand shaving and/or load management
activities?
A-EO-500-4. Customers with self-directed plans will be
eligible to calculate load management credits using the same methods as
providers. Staff believes load management only counts when it actually
conserves kilowatt hours.
- Q-EO-500-5. If a customer runs a
self-directed program and, in a given year, achieves greater savings
than required by legislation (i.e.: greater than 0.3 % in 2009), is
credit given for the additional savings?Can savings greater than
required in a given year be carried forward for credit on a future
year’s obligation? If so what percentage, and how many years? Is any
other “offset” contemplated?
A-EO-500-5. The statute is silent on self-directed
customers carrying forward excess savings. The Staff assumes that since
the providers can carry forward (See Section 83(3)), then self-directed
plans may also. The Commission will need to rule on this issue. Assuming
the Commission agrees, one restriction is necessary: since the
Self-directed plans are to be incorporated into the provider's EO plan
per Section 93(6), if the customer carries forward, then the provider
must carry forward the same amount.
- Q-EO-500-6. Can a provider carry over excess
natural gas savings? Only MWh savings, not MCfs, create EO credits, and
only EO credits may be carried forward.
A-EO-500-6. No. Only Mwh savings create certifiable
energy optimization credits because a certifiable energy optimization
credit can be substituted for a renewable energy credit (which is
electric only).
The legislation is silent on carrying forward natural
gas savings. However, Staff believes that for purposes of
meeting energy optimization performance standards (not creating
certifiable credits), excess natural gas savings should be able
to be carried forward in a manner analogous to Sec. 83(3)(a) electric
savings. Providers who are interested in carrying forward excess natural
gas savings for purposes of performance evaluation should request
approval in their state EO Plan filing.
- Q-EO-500-7. What does a new customer do? What do
they use for data points for prior years to record savings if there is
not prior year (new business example?) In a self-directed plan
option, what about new facilities? Would code be considered baseline
usage?
A-EO-500-7. Staff thinking on this is not fully
developed: Code is a possibility. So is extrapolating from use by
similar facilities, if any. If there are cases where code is the same as
best available practice, how do you start saving energy? Recommendations
on this issue are welcome in the context of the plan filings. It would
seem that the same answer (or range of options) should apply to
customers who participate in a provider’s plan and those who choose to
self-direct.
- Q-EO-500-8. Please provide an update of
the status of the Michigan Energy Savings Database, and how small
utilities may gain access to it. If a utility finds what it believes to
be problems with the database, may it substitute estimates it finds more
credible? Are these measure characterizations to be considered
definitive for estimating program savings?
A-EO-500-8. The statewide “deemed savings” database is
available now. Summary data is posted on the Spotlight section of the
Commission’s Electricity web page. Since the database is a statewide
collaborative effort, it is expected that any differences in opinion
about savings values would be worked out with the other collaborative
members and the database administrator. Staff believes the deemed
savings database should contain the definitive answer for measures
included in the database. Staff assumes that any utility that has
contributed toward the cost of the database would have the name and
contact information of the database administrator.
- Q-EO-500-9. There may be a particular
situation where the average isn’t applicable. For instance, maybe you
know that CFLs are used for 8 hours/day rather than the average of 2
hours/day.
A-EO-500-9. The database should accommodate variable
hours of operation. If there is a variation not represented in the
database this should be brought up in the collaborative evaluation
working group. There may also be more generic issues or processes that a
provider may wish to include in its plan filing.
- Q-EO-500-10. Regarding reporting MWh
sales based upon either (1) prior year’s “weather-normalization” or
(2) a three-year rolling average. For prior year’s weather-normalization
we do not have a 20-year history that we can use to base our
weather-normalization factor upon. We believe that actual prior
year’s MWh sales would be the most accurate yearly data to base our
renewable energy portfolio requirements on and therefore, we will be
requesting to use this method to calculate our renewable energy
portfolio.
However, if we would be provided the yearly
weather-normalized factor, in a timely manner, for each
investor-owned utility (Consumers Energy and Detroit Edison), we would
consider the prior year’s weather-normalization method. Since we serve
member-customers in both Consumers Energy and Detroit Edison service
territories, would it be possible to use the incumbent utilities
weather-normalized factor and apply that factor to our MWh sales to come
up with our prior year’s reporting requirement? If that would be a
possibility, where and when would we be able to receive these factors on
a yearly basis?
A-EO-500-10. Staff does not dictate the methodology for
weather-normalization. Providers need to work this out for, or among
themselves.
- Q-EO-500-11. Can 2008 energy savings from
self-directed customers be counted toward the 2009 target?
A-EO-500-11. Actually the first target is for the [2008
-2009] biennium. Staff interprets the statute as providing that
self-directed customers can include in their filed plan savings for both
years in meeting their 0.3% of base-year 2007 target. This is not the
same for providers. Even though the first target includes the 2008-2009
biennium, providers can only include energy efficiency measures that
were directly related to their approved EO plan.
Note Sec. 77(1) "…an electric provider's energy
optimization programs under this subpart shall collectively achieve the
following energy savings: (a) biennial incremental savings in 2008-2009
equivalent to 0.3% of total annual retail electricity sales in megawatt
hours in 2007."
- Q-EO-500-12. Clarify how far
back savings from existing energy optimization projects can be counted
toward meeting 2009 targets .
A-EO-500-12. The PA 295 Energy Optimization program is
an incremental savings program. See Sec. 77(1) referenced above and Sec
93 (5)(a)which states, "The self-directed plan shall outline how the
customer intends to achieve the incremental energy savings specified in
the self-directed plan." Since the base year for the 2008-2009 biennium
is 2007, January 1, 2007 becomes a hard cut-off date. Any measure
operational before Jan 1, 2007 is fully included in the customer's
base-year electric purchases.
Thus, savings produced by the measure in 2008, 2009 or
thereafter are not incremental savings and do not count toward the
target. If the measure was operational at some point during 2007, a
portion of the annual savings is included in the base year. For example,
if the measure was operational on October 1, 2007, 3/12 of the annual
savings is in the base year, and therefore 9/12 of the savings during
2008, 2009, or thereafter, qualifies as incremental savings.
- Q-EO-500-13. Does the Commission propose
to establish standardized inputs for use in applying the Utility System
Resource Cost Test (USRCT), or other tests that the Commission requires
utilities to conduct in evaluating the cost-effectiveness of their
programs? If so, when, and through what process?
A-EO-500-13. There is enough documentation regarding the
USRCT test that providers can determine the inputs from available data.
Staff can provide assistance if needed.
- Q-EO-500-14. Would individual entities
within a joint program need to meet the goals or can one entity
over-achieve and apply those saving towards under achieving
entities?
A-EO-500-14. Each entity must separately meet goals but
costs can be distributed to all entities as long as that approach is
specified in the plan.
TOP
|
|
U-15800 Order Clarifications (600)
|
Contact: Janet Hanneman |
- Q-EO-600-1 Commission directs the providers to
work with the Staff to establish a link from the MPSC web site to a site
where posted savings values can be viewed within 30 days after the
database becomes operational." Please define operational.
A-EO-600-1. Staff defines “operational” to mean when the
database is up and running, and can be made available to the public via
the internet.
- Q-EO-600-2. Page 40 regarding low income
residential customers - "MPSC expects creative/focused efforts to target
EO program services to distinct subsets of the low income population,
which may entail different services." Are there any existing low income
energy optimization programs in other states that could be cited as
examples?
A-EO-600-2. Staff is aware of comparative analyses of
low-income energy optimization programs completed by the American
Council for an Energy Efficient Economy (ACEEE; http://www.aceee.org/), and the
Low-Income Heating Energy Assistance Program (LIHEAP) Clearinghouse of
the National Center for Appropriate Technology (NCAT; http://www.ncat.org/). Staff recommends
that providers and interested parties review those sources for
information, and Staff invites all interested parties to share
additional references of examples of best practices.
- Q-EO-600-3. In developing an EO
plan, can the City of Detroit Public Lighting Department (a general fund
department of the City of Detroit, not a Board nor Authority) aggregate
the various energy efficiency activities that the various City of
Detroit departments/agencies are already conducting, to serve as the
DPLD‑controlled and -implemented plan, within the meaning of the
Act? Would such an aggregation of other City energy efficiency
programs serve as DPLD's self-directed EO plan (rather than DTE
separately charging DPLD, for DPLD’s participation in DTE’s EO program
activities)?
A-EO-600-3. No. Only to the extent that City of Detroit
energy efficiency programs are directly serving DPL itself or DPL
customers.
- Q-EO-600-4. In Section 45(5)( c) of PA 295, how
will savings from EO programs be calculated to be shown on a customer’s
bill? Does this use generic coal plant as a comparison?
A-EO-600-4. The savings (avoided cost) shown on the
customer bills will be based on the “guidepost rate” developed by the
Staff and the providers pursuant to the process described on page 24 of
the Temporary Order. This number must be forwarded to the Commission by
January 30, 2009. See pages 38 and 39 of the Temporary Order for further
discussion about information required on customer bills.
- Q-EO-600-5. In the case of small
utilities, is it possible to meet the obligation to provide customer
class equity in EO expenditures over a two or three year period? Our
largest customer class is residential meters and want to average costs
over several years.
- A-EO-600-5. Staff believes that is reasonable. The Act
says, “to the extent possible” the money collected should be used to
provide EO services to the customer class that paid it.
- Q-EO-600-6. Heat pumps use more
electricity but save total energy usage. Would they qualify for an
Energy Optimization program?
A-EO-600-6. Staff believes groundwater or ground heat
pump systems may qualify for Energy Optimization, but probably not a
straight heat pump. But we will have to look at the savings for the
plans.
- Q-EO-600-7. We have five different
residential rates. Is each rate supposed to show the Energy Optimization
reductions, i.e., 23%, or is the rate class considered as a whole?
A-EO-600-7. The rate class is considered as a whole.
- Q-EO-600-8. PA 295 divides customers into
three categories. Do municipals have discretion to place customers into
a class that they feel is more appropriate based on usage? Example: Can
pole barns be put into residential?
A-EO-600-8. The Commission spoke to this in the
Temporary Order with regard to extremely small commercial customers.
Providers, especially municipals, have the flexibility to treat that
customer as a residential customer. The Commission asked the providers
to review this issue as they put together their plans.
- Q-EO-600-9. Could we use EO funds to
install energy efficient streetlights?
A-EO-600-9. The plan was designed to conserve energy for
retail customers. If you have retail customers with streetlights, then
you can use the EO funding to operate a program which would change out
those lights. This includes the example of a city government that is a
retail customer of a municipal utility.
TOP
|
|